Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Naming Alarm Inputs 15-45
where
Examples
X To configure a severity level for alarm inputs for a
specific alarm
Use the following command syntax:
Syntax ldam alarm <alarm_name> trap severity <severity_level>
ldam alarm port <
port_number> point <point_number> trap
severity <
severity_level>
where
Examples
alarm_name Specifies an Alarm Input Name. The value of alarm_
name can be a descriptive name or a default name.
port_number Specifies the LDAM port number.
point_number Specifies the point on which you want to change the
fault state. Options are 1 and 2.
open The point will be in Alarm when it is open. This is the
default setting.
closed The point will be in Alarm when it is closed.
Config:0 >>ldam alarm SafedepositDoor fault state open
Config:0 >>ldam alarm 5_1 fault state closed
Config:0 >>ldam alarm port 2 point 1 fault state open
alarm_name Specifies an Alarm Input Name. The value of alarm_
name can be a descriptive name or a default name.
port_number Specifies the LDAM port number.
point_number Specifies the point on which you want to set trap
severity; either 1 or 2.
severity_level SNMP Trap Severity Level used when SNMP Traps are
sent for faults detected by the specified Alarm Inputs.
The allowable values are
Informational,
Warning, Minor, Major, and Critical. The
default is
Minor.
Config:0 >>ldam alarm SafedepositDoor trap severity critical
Config:0 >>ldam alarm 5_1 trap severity informational
Config:0 >>ldam alarm port 2 point 1 trap severity minor