Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Naming Alarm Inputs 15-43
X To configure an alarm input description string for a
specific alarm
Use the following command syntax:
Syntax ldam alarm <alarm_name> description <string>
ldam alarm port <
port_number> point <point_number>
description <
string>
where
Examples
X To default the description for an alarm input
1. Use the following command syntax to default the
description for an alarm input for a specific alarm:
Syntax ldam alarm <alarm_name> description <string>
2. Use the following command syntax to default the
description for an alarm input for multiple alarms:
Syntax ldam alarm port <port_number> slot [<slot_list>|all]
point [<
point_list>|all] default description <string>
where
alarm_name Specifies an Alarm Input Name. The default name for
an alarm input or control output is canonically derived
from the port number and point number.
port_number Specifies the LDAM port number.
point_number Specifies point on which you want to configure a
description string. Options are 1 and 2.
string The description of the alarm input (a maximum of 63
characters long).
Config:0 >>ldam alarm 5_1 description lab door 1
Config:0 >>ldam alarm 3_2 description lab door 2
Config:0 >>ldam alarm port 2 point 1 description lab1
alarm_name Specifies an Alarm Input Name. The default name for an
alarm input is canonically derived from the port number
and point number. For example, the default name for
the 1st alarm input on port 5 is 5_1.
port_number Specifies the LDAM port number.
Przeglądanie stron 430