Configuring the Trigger-Action Feature
Guidelines for Creating or Modifying Actions 11-13
X To monitor the power threshold based on the sum of
the load on multiple power units attached to an LX
L This command applies to all power units.
Execute the power port async total <port-list> load
<|> <threshold_number> [hysteresis <hysteresis_
number>] command to define a threshold (for Power Control
4800, 5150, and 5250 series) to compare the current total
load against:
Example Trigger_TestA:0 >>power port async total 8-12 load
< 8 hysteresis 1
If the defined threshold is exceeded, the appropriate action is
executed when the rule is enabled. Valid threshold values are
in the range from 0.0 to 65534.9. Valid hysteresis values are
in the range is 0.0 to 9.9 (note that you can use decimals).
X To configure a power trigger
Execute the power regulator command to specify the
status of the internal power supply’s functionality when
connected to the LX internals:
Example Trigger_PowerSupplyA:0 >>power regulator A status
restored
L You cannot use the trigger-action trigger types
"power" and "power regulator" on the LX-7304T.
A Power Port
Async Total
Load Trigger
is used to
perform
monitoring on
the total load
against a given
threshold.
A Power
Trigger
is used to
initiate an
Action in
response to
a power reading
or condition.