Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Configuring the Fault State for Alarm Inputs 15-11
where
Example
Configuring the Fault State for Alarm Inputs
Use the following commands to configure the fault state for
Alarm Inputs for a specific alarm or for multiple alarms.
X To configure the fault state for alarm inputs for a
specific alarm
Use the following command syntax:
Syntax hdam alarm <alarm_name> fault state [open|closed]
alarm_name Specifies an Alarm Input Name. The value of name can
be a descriptive name or a default name.
port_number Specifies the LX HDAM port managing the LX-7204T/
7304T.
slot_list Specifies a list of Slots on which you want to set the
debounce interval. The list can contain single items, lists
(such as 1,3,4) or ranges (such as 1-4), or a
combination.
point_list Specifies a list of Points on which you want to set the
debounce interval. The list can contain single items, lists
(such as 1,3,4) or ranges (such as 1-32), or a
combination.
all
The debounce interval specified in this command will
apply to all Slots or Points (or both) managed by this LX
Master Unit.
time Specifies the debounce interval, in milliseconds. The
allowable values are 0—1,800,000 milliseconds (1800
seconds or 30 minutes). The default is 0.
Config:0 >>hdam alarm 5_2_31 debounce 300
Config:0 >>hdam alarm port 2 slot 1-4 point 1,2,6-18 debounce 400