Configuring Alarming with LX-7204T/7304T Sensor Manager and LDAM
Resetting Alarm Inputs to the Defaults 15-15
Example
Resetting Alarm Inputs to the Defaults
Use the following commands to reset Alarm Inputs to the default
settings for a specific alarm or for multiple alarms.
X To reset the alarm input to default for a
specific point
Use the following command syntax
Syntax hdam alarm <alarm_name> default point
X To reset alarm inputs to defaults for multiple points
Use the following command syntax:
Syntax hdam alarm port <port_number> slot [<slot_list>|all] point
[<
point_list>|all] default point
where
Config:0 >>hdam alarm port 2 slot 1,2 point 1,2,3,4 default nam
Config:0 >>hdam alarm port 2 slot 1-4 point 6-18 default name
Config:0 >>hdam alarm port 2 slot all point all default name
Config:0 >>hdam alarm port 2 slot 1-4 point 6-18 default name
Config:0 >>hdam alarm fan_window default name
alarm_name The name of the alarm which you want to default. This
entry is in the order port_slot_alarm (e.g., 5_2_31, or
BankVaultDoor).
port_number Specifies the HDAM port managing the 7204T.
slot_list Specifies a list of Slots whose points you want to
default. The list can contain single items, lists (such as
1,3,4) or ranges (such as 1-4), or a combination.
point_list Specifies a list of Points to default. The list can contain
single items, lists (such as 1,3,4) or ranges (such as 1-
32), or a combination.
all
The default command will apply to all Slots or Points
(or both) managed by this LX Master Unit.